The LGP3001bi makes available a charging power of 3 kW. Active power factor correction (PFC) provides for sinusoidal power consumption.
Electrical Data
| Input Variables | |
|---|---|
| Input voltage | 230 V, 50 Hz (40 Hz - 70 Hz) |
| Under-/ overvoltage switch off (option: D) | -30 % / 35 % |
| Input current | <16 A, integrated PFC (Power Factor Correction) |
| Input current limit | parameters can be set separately for each operating state |
| Output levels (at 70 °C) | |
| Rated output power | 3000 W |
| Output voltage | 28.0 V IU charge (temperature-controlled) |
| Inverter Operation | |
| Input levels | |
| Input voltage | 24 V |
| Undervoltage / overvoltage shutdown | -30 % / 35 % |
| Output levels (at 70 °C) | |
| Rated output power | 3000 W |
| Output voltage | 230 V, 50 Hz (-30 % / 35 %) |
| General Electrical Data | |
| Rated efficiency | >90 % |
| Galvanic isolation | between interfaces, input and output |
| Radio interference | EN 50121-3-2 |
| Potential-free message | 3 message outputs (changeover contact max. 30 V, 0.5 A) |
| Control inputs | 2 control inputs (24 V) |
| Communication | CAN-bus, RS232 (service interface) |
| Fault memory | present |
Mechanical Data
| Display | 4-line LCD |
| Interfaces | 24 V on-board grid and starter battery: bolt terminals CAN + service interface: D-SUB (9-pin) all other interfaces: WAGO tension-spring terminals |
| Ambient temperature | -25 °C to +70 °C (EN 50155 Tx) |
| Cooling | Convection; optional fan kit |
| Note regarding cooling | do not cover the heat sink; it must be possible for natural convection to occur. |
| Protection class | IP20 |
| Noise emission | noiseless; <45 dB with fan operation with opt. fan kit |
| Casing | 19" rack-mount module |
| Weight | 25 kg |
| Color | RAL7035 |
Subject to change without prior notice (10/2010)
Datasheet
| Datasheet LGP3001biFormat: